CVE-2017-13997 Information

Description

A Missing Authentication for Critical Function issue was discovered in Schneider Electric InduSoft Web Studio v8.0 SP2 or prior and InTouch Machine Edition v8.0 SP2 or prior. InduSoft Web Studio provides the capability for an HMI client to trigger script execution on the server for the purposes of performing customized calculations or actions. A remote malicious entity could bypass the server authentication and trigger the execution of an arbitrary command. The command is executed under high privileges and could lead to a complete compromise of the server.

CVSS Vector

CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

Reference

http://www.securityfocus.com/bid/100952 https://ics-cert.us-cert.gov/advisories/ICSA-17-264-01

Attack Complexity

LOW

Privileges Required

NONE

User Interaction Required

NONE

Scope

NONE

Confidentiality Impact

UNCHANGED

Integrity Impact

HIGH

Availability Impact

HIGH

Base Score

HIGH

Base Severity

9.8