CVE-2017-14470 Information

Description

An exploitable access control vulnerability exists in the data program and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information modification of settings or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG or RUN Description: The value 0xffffffff is considered NaN for the Float data type. When a float is set to this value and used in the PLC a fault is triggered. NOTE: This is not possible through RSLogix.

CVSS Vector

CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

Reference

https://www.talosintelligence.com/vulnerability_reports/TALOS-2017-0443

Attack Complexity

LOW

Privileges Required

NONE

User Interaction Required

NONE

Scope

NONE

Confidentiality Impact

UNCHANGED

Integrity Impact

HIGH

Availability Impact

HIGH

Base Score

HIGH

Base Severity

9.8

Share on: