Rockwell Automation MicroLogix 1400 Controllers and 1756 ControlLogix Communications Modules An unauthenticated remote threat actor could send a CIP connection request to an affected device and upon successful connection send a new IP configuration to the affected device even if the controller in the system is set to Hard RUN mode. When the affected device accepts this new IP configuration a loss of communication occurs between the device and the rest of the system as the system traffic is still attempting to communicate with the device via the overwritten IP address.
CVSS Vector
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H
Reference
http://www.securityfocus.com/bid/106132 https://ics-cert.us-cert.gov/advisories/ICSA-18-310-02
Attack Complexity
LOW
Privileges Required
NONE
User Interaction Required
NONE
Scope
NONE
Confidentiality Impact
CHANGED
Integrity Impact
NONE
Availability Impact
NONE
Base Score
HIGH
Base Severity
8.6