CVE-2019-13927 Information
Description
A vulnerability has been identified in Desigo PX automation controllers PXC00-E.D PXC50-E.D PXC100-E.D PXC200-E.D with Desigo PX Web modules PXA40-W0 PXA40-W1 PXA40-W2 (All firmware versions V6.00.320) Desigo PX automation controllers PXC00-U PXC64-U PXC128-U with Desigo PX Web modules PXA30-W0 PXA30-W1 PXA30-W2 (All firmware versions V6.00.320) Desigo PX automation controllers PXC22.1-E.D PXC36-E.D PXC36.1-E.D with activated web server (All firmware versions V6.00.320). The device contains a vulnerability that could allow an attacker to cause a denial of service condition on the device’s web server by sending a specially crafted HTTP message to the web server port (tcp/80). The security vulnerability could be exploited by an attacker with network access to an affected device. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise the availability of the device’s web service. While the device itself stays operational the web server responds with HTTP status code 404 (Not found) to any further request. A reboot is required to recover the web interface. At the time of advisory publication no public exploitation of this security vulnerability was known.
CVSS Vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L
Reference
https://cert-portal.siemens.com/productcert/pdf/ssa-898181.pdf
Attack Complexity
LOW
Privileges Required
NONE
User Interaction Required
NONE
Scope
NONE
Confidentiality Impact
UNCHANGED
Integrity Impact
NONE
Availability Impact
NONE
Base Score
LOW
Base Severity
5.3
Share on: