CVE-2023-2071 Information
Description
Rockwell Automation FactoryTalk View Machine Edition on the PanelView Plus improperly verifies user’s input which allows unauthenticated attacker to achieve remote code executed via crafted malicious packets. The device has the functionality through a CIP class to execute exported functions from libraries. There is a routine that restricts it to execute specific functions from two dynamic link library files. By using a CIP class an attacker can upload a self-made library to the device which allows the attacker to bypass the security check and execute any code written in the function.
CVSS Vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Reference
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1140724
Attack Complexity
LOW
Privileges Required
NONE
User Interaction Required
NONE
Scope
NONE
Confidentiality Impact
UNCHANGED
Integrity Impact
HIGH
Availability Impact
HIGH
Base Score
HIGH
Base Severity
9.8